This ECR proposes to add monitoring software to the TwinCAT system running on PLC1 which monitors the master bus device (i.e., the Ethernet interface). The following monitors would be added:
- A monitor for the working counters which check that each EtherCAT frame has successfully completed its round-trip though all addressed terminals.
- A status monitor indicating, if the master device is up and running.
- A status monitor indicating a link error (i.e., a cable got unhooked).
- A status monitor indicating, if one of the terminals is not in OP mode.
- A status monitor indicating, if the number of active terminals is different from the configuration (unexpected hardware change).
- A status monitor indicating a timing error.
- A status monitor indicating, if frames were lost.
- Statistics counters monitoring the EtherCAT frames.